The UNIVERSAL16 module comprises 8 differential analog inputs, 6 digital inputs, 1digital output and 1 thermocouple input, with automatic cold junction compensation and open circuit thermocouple monitoring. |
![]() |
|||
Specification |
|
Isolation |
500V DC |
Analog inputs: |
|
Number of Channels |
8 |
Input type |
4-20mA (developing 1-5V across 250R) |
Input Protection |
30V pk-pk |
Input Impedance |
108 Ohm (1K Ohm to supply rail in over voltage condition) |
Sampling rate |
160 channels/sec |
Converter Type |
13 bit SAR with auto zero |
Accuracy |
0.05% or better |
Zero drift |
1.2uV / ºC |
CMR |
100 dB |
Digital inputs: |
|
Number of Channels |
6 |
Inputs |
Logic 1 <1.0V Logic 0 >3.0V (30V max) |
Internal Pull Up |
18V @ 0.5ma per channel |
Event Counters |
2 bit 10Hz on every input. Minimum input pulse 50ms |
Programmable Filters |
Programmable from 0 to 5 seconds in 50ms steps for each counter |
Digital Outputs: |
|
Number of Channels |
1 |
Output |
Logic 1, 18V (10mA max) Logic 0, 0V |
Event Driven Outputs |
This channel may be configured as a counter driven output controlled by events on digital input channel 0. |
Themocouple Input: |
|
Number of Channels |
1 |
Thermocouple Types |
J, K, R, S, T, B, E |
Call us now on: 0161 480 3163 or click here to email
UNIVERSAL16
Sixteen channel universal I/O module